Siemens SIRIUS 3RV2031 / 3RV2032 size S2 protection device for motor protection, class 10, without auxiliary switches. Available for rated currents 14–80 A with adjustable thermal overload release and fixed instantaneous (short-circuit) release.
Technical data
| Series | 3RV2031 / 3RV2032 |
|---|---|
| Size | S2 |
| Application | Motor protection |
| Trip class | 10 |
| Auxiliary switch | none |
| Rated current range | 14–80 A |
| Mounting | Screw or snap-on mounting on TH35 DIN rail |
| Connection | Screw terminals |
| Standard | IEC 60947-2, IEC 60947-4-1 |
Article numbers
| In (A) | Motor rating (kW, 400 V) | Setting range (A) | Instantaneous release (A) | Icu 400 V (kA) | Version | Screw |
|---|---|---|---|---|---|---|
| 14 | 5.5 | 9.5–14 | 208 | 65 | – | 3RV2031-4SA10 |
| 17 | 7.5 | 12–17 | 260 | 65 | – | 3RV2031-4TA10 |
| 20 | 7.5 | 14–20 | 260 | 65 | – | 3RV2031-4BA10 |
| 25 | 11 | 18–25 | 325 | 65 | – | 3RV2031-4DA10 |
| 32 | 15 | 22–32 | 416 | 65 | – | 3RV2031-4EA10 |
| 36 | 18.5 | 28–36 | 520 | 65 | – | 3RV2031-4PA10 |
| 40 | 18.5 | 32–40 | 585 | 65 | – | 3RV2031-4UA10 |
| 45 | 22 | 35–45 | 650 | 65 | – | 3RV2031-4VA10 |
| 52 | 22 | 42–52 | 741 | 65 | – | 3RV2031-4WA10 |
| 59 | 30 | 49–59 | 845 | 65 | – | 3RV2031-4XA10 |
| 65 | 30 | 54–65 | 845 | 65 | – | 3RV2031-4JA10 |
| 73 | 37 | 62–73 | 949 | 65 | – | 3RV2031-4KA10 |
| 80 | 37 | 70–80 | 1040 | 65 | – | 3RV2031-4RA10 |
| 25 | 11 | 18–25 | 325 | 50 | special conditions down to −50 °C | 3RV2031-4DA10-0BA0 |
| 32 | 15 | 22–32 | 416 | 50 | special conditions down to −50 °C | 3RV2031-4EA10-0BA0 |
| 45 | 22 | 34–45 | 650 | 50 | special conditions down to −50 °C | 3RV2031-4VA10-0BA0 |
| 65 | 30 | 54–65 | 845 | 65 | special conditions down to −50 °C | 3RV2031-4JA10-0BA0 |
| 14 | 5.5 | 9.5–14 | 208 | 100 | increased switching capacity | 3RV2032-4SA10 |
| 17 | 7.5 | 12–17 | 260 | 100 | increased switching capacity | 3RV2032-4TA10 |
| 20 | 7.5 | 14–20 | 260 | 100 | increased switching capacity | 3RV2032-4BA10 |
| 25 | 11 | 18–25 | 325 | 100 | increased switching capacity | 3RV2032-4DA10 |
| 32 | 15 | 22–32 | 416 | 100 | increased switching capacity | 3RV2032-4EA10 |
| 36 | 18.5 | 28–36 | 520 | 100 | increased switching capacity | 3RV2032-4PA10 |
| 40 | 18.5 | 32–40 | 585 | 100 | increased switching capacity | 3RV2032-4UA10 |
| 45 | 22 | 35–45 | 650 | 100 | increased switching capacity | 3RV2032-4VA10 |
| 52 | 22 | 42–52 | 741 | 100 | increased switching capacity | 3RV2032-4WA10 |
| 59 | 30 | 49–59 | 845 | 100 | increased switching capacity | 3RV2032-4XA10 |
| 65 | 30 | 54–65 | 845 | 100 | increased switching capacity | 3RV2032-4JA10 |
| 73 | 37 | 62–73 | 949 | 100 | increased switching capacity | 3RV2032-4KA10 |
| 80 | 37 | 70–80 | 1040 | 100 | increased switching capacity | 3RV2032-4RA10 |
Motor ratings are guide values for 4-pole standard motors at 50 Hz 400 V AC; the actual starting and rated data of the motor must be considered. Versions for special conditions down to −50 °C have limited mechanical endurance and no UL/CSA, ATEX or IECEx approval (catalog footnote). Auxiliary switches and other accessories are ordered separately.
Technical data and article numbers are based on Siemens catalog IC 10 · 2026 (chapter 7, protection equipment) and are for information only. Image is representative.
For price, stock and lead time, use the Request a Quote button or call +90 533 945 27 94. Sending the article number is enough.
Tags: 3RV2031 / 3RV2032, siemens motor starter protector, 3RV2, circuit breaker, motor protection, 3RV2031-4SA10, 3RV2031-4TA10, 3RV2031-4BA10, 3RV2031-4DA10, 3RV2031-4EA10, 3RV2031-4PA10, 3RV2031-4UA10, 3RV2031-4VA10, 3RV2031-4WA10, 3RV2031-4XA10, 3RV2031-4JA10, 3RV2031-4KA10, 3RV2031-4RA10, 3RV2031-4DA10-0BA0, 3RV2031-4EA10-0BA0, 3RV2031-4VA10-0BA0, 3RV2031-4JA10-0BA0, 3RV2032-4SA10, 3RV2032-4TA10, 3RV2032-4BA10, 3RV2032-4DA10, 3RV2032-4EA10, 3RV2032-4PA10, 3RV2032-4UA10, 3RV2032-4VA10, 3RV2032-4WA10, 3RV2032-4XA10, 3RV2032-4JA10, 3RV2032-4KA10, 3RV2032-4RA10