Siemens SIRIUS 3RR2 Current Monitoring Relay (1.6–80 A)

Siemens SIRIUS 3RR2 Current Monitoring Relay (1.6–80 A)

  • Brand: Siemens
  • Product Code: 3RR2 current monitoring relay

Prices are prepared per project according to capacity, energy type and delivery terms.

Siemens SIRIUS 3RR2 current monitoring relays mount directly on 3RT2 contactors and 3RU2 overload relays to monitor motor current: detect underload, belt breakage, dry running or overload.

Technical data

Series3RR21 / 3RR22 / 3RR24
Product typeCurrent monitoring relay, mounts directly on 3RT2 contactor / 3RU2 overload relay
Measuring range1.6–16 A (S00), 4–40 A (S0), 8–80 A (S2)
MonitoringUnder/overcurrent, active or apparent current, phase sequence, residual current, blocking current (by model)
Output1 CO (+ 1 semiconductor output, 3RR22/3RR24)
CommunicationIO-Link (3RR24)
ConnectionScrew or spring-loaded terminals

Article numbers

VersionSizeMeasuring rangeHysteresisSupplyScrewSpring-loaded
3RR21 Basic (analog, 2-phase, apparent current)S001.6–16 A6.25% of threshold24 V AC/DC3RR2141-1AA303RR2141-2AA30
3RR21 Basic (analog, 2-phase, apparent current)S001.6–16 A6.25% of threshold24–240 V AC/DC3RR2141-1AW303RR2141-2AW30
3RR21 Basic (analog, 2-phase, apparent current)S04–40 A6.25% of threshold24 V AC/DC3RR2142-1AA303RR2142-2AA30
3RR21 Basic (analog, 2-phase, apparent current)S04–40 A6.25% of threshold24–240 V AC/DC3RR2142-1AW303RR2142-2AW30
3RR21 Basic (analog, 2-phase, apparent current)S28–80 A6.25% of threshold24 V AC/DC3RR2143-1AA303RR2143-3AA30
3RR21 Basic (analog, 2-phase, apparent current)S28–80 A6.25% of threshold24–240 V AC/DC3RR2143-1AW303RR2143-3AW30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S001.6–16 A0.1–3 A24 V AC/DC3RR2241-1FA303RR2241-2FA30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S001.6–16 A0.1–3 A24–240 V AC/DC3RR2241-1FW303RR2241-2FW30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S04–40 A0.1–8 A24 V AC/DC3RR2242-1FA303RR2242-2FA30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S04–40 A0.1–8 A24–240 V AC/DC3RR2242-1FW303RR2242-2FW30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S28–80 A0.2–16 A24 V AC/DC3RR2243-1FA303RR2243-3FA30
3RR22 Standard (digital, LCD, 3-phase, active/apparent current)S28–80 A0.2–16 A24–240 V AC/DC3RR2243-1FW303RR2243-3FW30
3RR24 IO-Link (digital, LCD, 3-phase, counters)S001.6–16 A0.1–3 A24 V DC3RR2441-1AA403RR2441-2AA40
3RR24 IO-Link (digital, LCD, 3-phase, counters)S04–40 A0.1–8 A24 V DC3RR2442-1AA403RR2442-2AA40
3RR24 IO-Link (digital, LCD, 3-phase, counters)S28–80 A0.2–16 A24 V DC3RR2443-1AA403RR2443-3AA40

Technical data and article numbers are based on Siemens catalog IC 10 · 2026 (chapter 10, monitoring and control devices) and are for information only. Image is representative.

For price, stock and lead time, use the Request a Quote button or call +90 533 945 27 94. Sending the article number is enough.

Tags: 3RR2 current monitoring relay, siemens current monitoring relay, 3RR2, undercurrent relay, 3RR2141-1AA30, 3RR2141-2AA30, 3RR2141-1AW30, 3RR2141-2AW30, 3RR2142-1AA30, 3RR2142-2AA30, 3RR2142-1AW30, 3RR2142-2AW30, 3RR2143-1AA30, 3RR2143-3AA30, 3RR2143-1AW30, 3RR2143-3AW30, 3RR2241-1FA30, 3RR2241-2FA30, 3RR2241-1FW30, 3RR2241-2FW30, 3RR2242-1FA30, 3RR2242-2FA30, 3RR2242-1FW30, 3RR2242-2FW30, 3RR2243-1FA30, 3RR2243-3FA30, 3RR2243-1FW30, 3RR2243-3FW30, 3RR2441-1AA40, 3RR2441-2AA40, 3RR2442-1AA40, 3RR2442-2AA40, 3RR2443-1AA40, 3RR2443-3AA40